TACACS+ Technical Specifications
Authentication START Packet includes:
action = 1 (TAC_PLUS_AUTHEN_LOGIN)
priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN)
authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII)
service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN)
user = (entered username)
port = (access path into the Sentry)
rem_addr = ‘Sentry3_xxxxxx’ (xxxxxx is last six digits of MAC address)
data = ‘‘ (null)
NOTE: The password is sent in a CONTINUE packet.
Authorization REQUEST Packet includes:
authen_method = 6 (TAC_PLUS_AUTHEN_METH_TACACSPLUS)
priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN)
authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII)
authen_service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN)
user = (entered username)
port = (access path into the Sentry)
rem_addr = ‘Sentry3_xxxxxx’ (xxxxxx is last six digits of Ethernet MAC address)
service = ‘shell’ (for exec)
cmd = ‘‘ (null)
NOTE: The access paths into the Sentry which support TACACS+ are ‘Console’, ‘Telnet’, ‘SSH’, ‘HTTP’ and
‘HTTPS’. In the case of ‘Console’ and ‘Modem’, an administrator is allowed to rename these ports in which case the
assigned name is used.