Serial Port Administration
Creating a descriptive serial port name:
The Set Port Name command assigns a descriptive name to a serial port. You may use this name in
commands that require a port name as an alternative to using the port’s absolute name.
To create a port name:
At the Smart CDU: prompt, type set port name followed by the absolute outlet name, then a
descriptive name of up to 24 alphanumeric and other typeable characters - (ASCII 33 to 126 decimal)
are allowed; spaces are not allowed; port names are not case sensitive. Press Enter.
Example
The following command adds the descriptive name Rack1 to Console port:
Smart CDU: set port name console Rack1<Enter>
Setting the serial ports data-rate:
The Set Port Speed command sets the default data-rate for the serial port.
Valid data-rates are 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200.
To set the serial port data-rate:
At the Smart CDU: prompt, type set port speed, follow by the data-rate and press Enter.
Example
The following command sets the serial ports data-rate to 38400 BPS:
Smart CDU: set port speed 38400<Enter>
Enabling or disabling active signal checking for serial connections:
The Set Port DSRchk command enables or disables active signal checking for serial connections to
devices attached to any of the available serial ports.
To enable or disable active signal checking for serial connections:
At the Smart CDU: prompt, type set port dsrchk console, on or off, and press Enter.
Setting the serial port timeout value:
The Set Port Timeout command is used to set the serial port inactivity timeout period. The timeout
period defines the maximum period of inactivity before automatically closing the Pass-Thru session.
The valid range for the period parameter is 0 to 5 (in minutes). The default period is 5.
NOTE: Setting the timeout to ‘0’ disables the timer.
To set the serial port timeout value:
At the Smart CDU: prompt, type set port timeout, followed by a value from 0 to 5 (in minutes) and
press Enter.
Displaying serial port information:
The Show Ports command displays information about all serial ports. This information includes:
Serial port data rate
Descriptive port name, if applicable
DSR signal checking settings
To display serial port information:
At the Smart CDU: prompt, type show ports and press Enter.
Example
The following command displays all serial port information:
Smart CDU: show ports<Enter>
Serial Port Configuration
ALL Ports:
Baud Rate: 38400 Connection Timeout: 5 minutes
Port ID: Console Port Name: CONSOLE
DSR Check: ON