56 Advanced Operations Smart Cabinet Distribution Unit
Installation and Operations Manual
Status trap
A Status trap is generated when an error condition occurs on a tower, infeed, Environmental Monitor or
individual sensor. Status traps include the reported Status, the Location of the Sentry and identifier and
name of the affected tower, infeed, outlet, environmental monitor or sensor.
Any error state generates a Status trap and triggers the trap timer. A new trap is generated at the end of
every timer period until the Status returns to a non-error status. All status traps are enabled by default.
Tower Status traps
Status Error Description
Normal Tower is working correctly
NoComm x Communication to the tower has been lost
Infeed Status traps
Status Error Description
On Infeed is on
OffError x Infeed should be on but no current is sensed at the infeed
NoComm x Communication to the infeed has been lost
Environmental Monitor Status traps
Status Error Description
Normal Environmental Monitor is working correctly
NoComm x Communication to the Environmental Monitor has been lost
Temperature/Humidity Sensor Status traps
Status Error Description
Found The sensor has been detected
NotFound No sensor has been detected
Lost x Sensor initially detected but communication to the sensor has been lost
NoComm x Communication to the sensor has been lost
NOTE: Traps are generated according to a hierarchical architecture; i.e., if a Tower Status enters a trap condition, only the
Tower Status trap will be generated. Infeed, Outlet, Environmental Monitor or Sensor Status and Temp and Humid traps
will be suppressed until the Tower Status returns to Normal.
Load Trap
The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load
traps include the reported input load, load status, Location of the Sentry, and identifier and name of the
affected infeed.
Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of
every timer period until the Load returns to a non-error status.
Load traps
Status Error Description
Normal Infeed is on and within preset thresholds
NotOn Infeed is off
Reading Non-error state – Load status currently being read
LoadHigh x Infeed current load exceeds preset threshold
OverLoad x Infeed current load exceeds the measurable range for the infeed
ReadError x Unable to read Load status
NoComm x Communication to the infeed has been lost